BS 6622 Single Core Unarmoured (Copper Wire Screened) 6.6kV XLPE Stranded Aiuminium Conductors
Construction
| cross-sectional area mmsq | Minimum average thickness of insulation mm | Nominal diameter over insulation  
 | Nominal area of copperwire screen mmsq | Nominal average thickness of PVC oversheath  | Nominal overall diameter of cable mm | 
| 70 | 2.5 | 16.8 | 16.0 | 1.7 | 23.5 | 
| 95 | 2.5 | 18.5 | 16.0 | 1.7 | 25.4 | 
| 120 | 2.5 | 20.0 | 16.0 | 1.8 | 26.9 | 
| 150 | 2.5 | 21.3 | 16.0 | 1.8 | 28.5 | 
| 185 | 2.5 | 23.1 | 16.0 | 1.9 | 30.3 | 
| 240 | 2.6 | 25.5 | 25.0 | 1.9 | 32.9 | 
| 300 | 2.8 | 28.3 | 25.0 | 2.0 | 35.9 | 
| 400 | 3.0 | 31.4 | 35.0 | 2.2 | 39.2 | 
| 500 | 3.2 | 34.7 | 35.0 | 2.6 | 42.8 | 
| 630 | 3.2 | 38.6 | 35.0 | 3.1 | 47.0 | 
Installation
| cross-sectional area mmsq | Approximate cable weight kg/m | Nominal drum length  | Minimum bending radius mm | Nominal internal diameter of ducts mm | 
| 70 | 0.7 | 1000 | 400 | 100 | 
| 95 | 0.8 | 1000 | 400 | 100 | 
| 120 | 1.0 | 1000 | 450 | 100 | 
| 150 | 1.1 | 500 | 450 | 100 | 
| 185 | 1.3 | 500 | 500 | 100 | 
| 240 | 1.5 | 500 | 500 | 100 | 
| 300 | 1.7 | 500 | 550 | 100 | 
| 400 | 2.2 | 500 | 600 | 100 | 
| 500 | 2.6 | 500 | 650 | 100 | 
| 630 | 3.1 | 300 | 750 | 100 | 
Electrical Performance
| cross-sectional area mmsq | Maximum DC resistance of conductor at 20 ¡æ uohms/m | Maximum AC resistance of conductor at 90 ¡æ uohms/m | Reactance at 50Hz  | Impedance at 50Hz uohms/m | Maximum Capacitace PF/m | Maximum charging current at normal voltage and frequency mA/m | 
| 70 | 443 | 568 | 111 | 580 | 371 | 0.45 | 
| 95 | 320 | 410 | 109 | 424 | 417 | 0.50 | 
| 120 | 253 | 325 | 105 | 342 | 459 | 0.55 | 
| 150 | 206 | 265 | 103 | 284 | 494 | 0.59 | 
| 185 | 164 | 211 | 99.5 | 233 | 543 | 0.65 | 
| 240 | 125 | 161 | 96.6 | 188 | 583 | 0.70 | 
| 300 | 100 | 130 | 94.7 | 161 | 602 | 0.72 | 
| 400 | 77.8 | 102 | 92.5 | 138 | 627 | 0.75 | 
| 500 | 60.5 | 81.0 | 90.7 | 122 | 654 | 0.79 | 
| 630 | 46.9 | 64.0 | 87.6 | 109 | 737 | 0.87 | 
Ratings
| Cross-sectional area  | Current Ratings | Short circuit ratings | |||
| Laid direct in ground  | Drawn into ducts  | Laid in air  | One second short circuit rating of conductor  | One second short circuit rating of copper per core  | |
| 70 | 210 | 215 | 240 | 6.3 | 2.6 | 
| 95 | 250 | 255 | 300 | 8.5 | 2.6 | 
| 120 | 280 | 285 | 335 | 11.0 | 2.6 | 
| 150 | 320 | 315 | 380 | 13.5 | 2.6 | 
| 185 | 360 | 350 | 435 | 17.0 | 2.6 | 
| 240 | 415 | 405 | 510 | 22.3 | 4.3 | 
| 300 | 475 | 455 | 600 | 28.0 | 4.3 | 
| 400 | 540 | 510 | 700 | 36.6 | 5.8 | 
| 500 | 610 | 570 | 810 | 46.2 | 5.8 | 
| 630 | 680 | 640 | 930 | 58.3 | 5.8 | 